Shock Hosting Outage History

Shock Hosting is up right now

Shock Hosting had 27 outages in the last 2 years totaling 24h 15m of downtime — averaging 1.1 incidents per month.

There were 27 Shock Hosting outages since February 9, 2025 totaling 24h 15m of downtime. Each is summarised below — incident details, duration, and resolution information.

Source: https://status.shockhosting.net

Major October 5, 2026

New York Datacenter Outage

Detected by Pingoru
Oct 05, 2026, 12:20 PM UTC
Resolved
Oct 05, 2026, 12:40 PM UTC
Duration
20m
Affected: Core (Website / Client Area )Core (VPS Control Panel )Locations ( New York)Core (Dedicated Control Panel )Core (DNS Cluster)
Timeline · 2 updates
  1. investigating Oct 05, 2026, 12:20 PM UTC

    We are currently investigating this incident.

  2. resolved Oct 05, 2026, 12:40 PM UTC

    This incident has been resolved. Our upstream network provider experienced a temporary outage.

Read the full incident report →

Minor September 27, 2026

Degraded Amsterdam Network Performance

Detected by Pingoru
Sep 27, 2026, 05:37 PM UTC
Resolved
Sep 28, 2026, 05:32 PM UTC
Duration
23h 55m
Affected: Locations ( Netherlands)
Timeline · 2 updates
  1. investigating Sep 27, 2026, 05:37 PM UTC

    We are investigating reports of degraded network performance and intermittent connectivity issues in Amsterdam.

  2. resolved Sep 28, 2026, 05:32 PM UTC

    Our upstream has implemented a fix for a flapping port on their end, we're no longer seeing packet loss on routes. Please contact our team if you're still experiencing any networking issues.

Read the full incident report →

Minor July 12, 2026

TX-K2 VPS Node CMOS Battery Replacement

Detected by Pingoru
Jul 12, 2026, 03:00 PM UTC
Resolved
Jul 12, 2026, 03:00 PM UTC
Duration
—
Timeline · 1 update
  1. resolved Jul 12, 2026, 03:00 PM UTC

    Type: Maintenance Duration: 15 minutes Affected Components: Dallas Jul 12, 15:00:01 GMT+0 - Identified - Maintenance is now in progress Jul 12, 15:15:15 GMT+0 - Completed - Maintenance has completed successfully. The battery has been replaced and the node is back online. Jul 10, 22:13:34 GMT+0 - Identified - Our monitoring system has alerted us to a degraded CMOS battery inside the TX-K2 VPS node, which is hosting at least one of your servers. We have scheduled our technician in Dallas to replace the battery on Sunday, July 12th at 10:00 AM CST. The TX-K2 VPS node will need to be shut down temporarily to facilitate the battery replacement, which should only take about 5 to 10 minutes. After the battery is replaced, the node will be powered back on, and all servers will boot back up automatically. Please let us know if you have any questions or concerns. Best regards, Shock Hosting Team [[email protected]](mailto:[email protected])

Read the full incident report →

Minor July 9, 2026

Emergency reboot (cPanel)

Detected by Pingoru
Jul 09, 2026, 02:55 PM UTC
Resolved
Jul 09, 2026, 02:55 PM UTC
Duration
—
Timeline · 1 update
  1. resolved Jul 09, 2026, 02:55 PM UTC

    Type: Maintenance Duration: 10 minutes Affected Components: Jacksonville, Seattle, Denver, Los Angeles, Chicago, Tokyo, Singapore, Coventry, Sydney, Warsaw, Paris, São Paulo, Dallas, Johannesburg, Frankfurt, New York, Romania, Netherlands Jul 9, 14:52:22 GMT+0 - Identified - To mitigate a newly disclosed vulnerability, all cPanel servers are being rebooted to apply the updated kernel. Jul 9, 14:55:01 GMT+0 - Identified - Maintenance is now in progress Jul 9, 15:05:00 GMT+0 - Completed - Maintenance has completed successfully

Read the full incident report →

Minor July 8, 2026

License error on cPanel/WHM

Detected by Pingoru
Jul 08, 2026, 09:30 PM UTC
Resolved
Jul 08, 2026, 09:30 PM UTC
Duration
—
Timeline · 1 update
  1. resolved Jul 08, 2026, 09:30 PM UTC

    Type: Incident Duration: 1 hour and 13 minutes Jul 8, 21:30:00 GMT+0 - Identified - cPanel may be inaccessible and show a license error. This appears to only affect the cPanel, WHM, and webmail user interfaces, with website functionality being unaffected. Sadly, this is an issue on cPanel's side that is affecting their licensing servers. They are aware of it and are addressing it. Jul 8, 22:42:34 GMT+0 - Resolved - cPanel has rolled out a fix and the user interfaces are now available again as servers complete the license checks.

Read the full incident report →

Major September 8, 2025

NY-S4 - Outage

Detected by Pingoru
Sep 08, 2025, 09:33 AM UTC
Resolved
Sep 08, 2025, 09:33 AM UTC
Duration
—
Timeline · 1 update
  1. resolved Sep 08, 2025, 09:33 AM UTC

    Type: Incident Duration: 1 hour and 1 minute Affected Components: New York Sep 8, 09:33:00 GMT+0 - Investigating - We are currently investigating an outage with NY-S4; it appears to be refusing to power up, so the DC tech will be investigating further. Sep 8, 10:34:00 GMT+0 - Resolved - The machine's power cables were reseated, and it is now booting up. All services should be back online.

Read the full incident report →

Minor September 2, 2025

West Chicago - PDU failure

Detected by Pingoru
Sep 02, 2025, 03:42 PM UTC
Resolved
Sep 02, 2025, 03:42 PM UTC
Duration
—
Timeline · 1 update
  1. resolved Sep 02, 2025, 03:42 PM UTC

    Type: Incident Duration: 19 minutes Affected Components: Chicago Sep 2, 15:42:33 GMT+0 - Identified - PDU-B in our West Chicago rack is currently experiencing failures, causing intermittent power; replacement is being arranged. Sep 2, 16:01:14 GMT+0 - Resolved - The PDU has been replaced; all affected services should be back online.

Read the full incident report →

Major September 1, 2025

Frankfurt - Outage

Detected by Pingoru
Sep 01, 2025, 11:06 AM UTC
Resolved
Sep 01, 2025, 11:06 AM UTC
Duration
—
Timeline · 1 update
  1. resolved Sep 01, 2025, 11:06 AM UTC

    Type: Incident Duration: 48 minutes Affected Components: Frankfurt Sep 1, 11:06:04 GMT+0 - Investigating - We are aware of an outage in Frankfurt and are investigating the cause. Sep 1, 11:54:33 GMT+0 - Resolved - Our datacenter provider claimed they had not received our monthly rent payment, but after we provided proof, they located the payment and restored our service.

Read the full incident report →

Minor August 25, 2025

DE-K1 VPS Node Memory Upgrade

Detected by Pingoru
Aug 25, 2025, 02:00 PM UTC
Resolved
Aug 25, 2025, 02:00 PM UTC
Duration
—
Timeline · 1 update
  1. resolved Aug 25, 2025, 02:00 PM UTC

    Type: Maintenance Duration: 1 hour Affected Components: Frankfurt Aug 25, 15:00:00 GMT+0 - Completed - Maintenance has completed successfully Aug 25, 14:00:00 GMT+0 - Identified - On Monday, August 25th, at approximately 4:00 PM CEST (GMT +2) we will be upgrading the memory capacity of the DE-K1 VPS node in Frankfurt. Unfortunately, the node needs to be removed from the server cabinet to perform the upgrade, so we expect about 30 to 60 minutes of downtime for this task to be completed. Please let us know if you have any questions or concerns. Aug 25, 14:00:01 GMT+0 - Identified - Maintenance is now in progress

Read the full incident report →

Major June 6, 2025

SG-S2 Server Outage

Detected by Pingoru
Jun 06, 2025, 05:10 AM UTC
Resolved
Jun 06, 2025, 05:10 AM UTC
Duration
—
Timeline · 1 update
  1. resolved Jun 06, 2025, 05:10 AM UTC

    Type: Incident Duration: 59 minutes Affected Components: Singapore Jun 6, 05:10:07 GMT+0 - Investigating - We are currently investigating this incident. Jun 6, 06:09:07 GMT+0 - Resolved - This outage was due to faulty memory causing the server to enter a boot loop. The server has been brought back online and we will schedule a replacement of the faulty memory as soon as possible.

Read the full incident report →

Minor May 28, 2025

Singapore - SG-K4 Memory Replacement

Detected by Pingoru
May 28, 2025, 06:00 AM UTC
Resolved
May 28, 2025, 06:00 AM UTC
Duration
—
Timeline · 1 update
  1. resolved May 28, 2025, 06:00 AM UTC

    Type: Maintenance Duration: 22 minutes Affected Components: Singapore May 28, 06:00:01 GMT+0 - Identified - Maintenance is now in progress May 28, 06:00:00 GMT+0 - Identified - 2 x memory DIMM's determined to be faulty will be replaced in SG-K4\. We expect approximately 30 to 60 minutes of downtime for this task to be completed. May 28, 06:21:44 GMT+0 - Completed - Maintenance has completed successfully.

Read the full incident report →

Minor March 29, 2025

Los Angeles - Rack Power Balancing

Detected by Pingoru
Mar 29, 2025, 01:00 PM UTC
Resolved
Mar 29, 2025, 01:00 PM UTC
Duration
—
Timeline · 1 update
  1. resolved Mar 29, 2025, 01:00 PM UTC

    Type: Maintenance Duration: 1 hour Affected Components: Los Angeles Mar 29, 13:00:01 GMT+0 - Identified - Maintenance is now in progress Mar 29, 14:00:00 GMT+0 - Completed - Maintenance has completed successfully Mar 29, 13:00:00 GMT+0 - Identified - On Saturday, March 29th at 6:00 AM Los Angeles time (PST) we will be moving the following VPS nodes to a different cabinet in the same datacenter (CoreSite LA2) to balance the power load: \- LA-K3 \- LA-K4 We anticipate about 30 minutes of downtime to fully shut down the nodes, move them to the other cabinet, and then power them back on. Please let us know if you have any questions or concerns.

Read the full incident report →