EX Networks incident

Power Incident - Virtus LON1 Enfield

Resolved after 8 hours 15 minutes, affecting Virtual Data Centre (vDC) - Virtus Enfield and Virtus LON1 Enfield, on October 22, 2026.

resolved Oct 22, 2026, 10:46 PM UTC

Full redundancy has now been restored, and as a precaution, a number of PDUs replaced in Virtus Enfield. EXN will continue investigations with Virtus over coming days, and a full PIR will be issued to affected clients.

Started
Oct 22, 2026, 02:31 PM UTC
Resolved
Oct 22, 2026, 10:46 PM UTC
Duration
8h 15m
Detected by Pingoru
Oct 22, 2026, 02:31 PM UTC

Affected components

Virtual Data Centre (vDC) - Virtus EnfieldVirtus LON1 Enfield

Update timeline

  1. investigating Oct 22, 2026, 02:31 PM UTC

    EXN is currently investigating a potential power issue affecting Datahall 3 at Virtus LON1 Enfield. All racks is this Datahall are dual-fed (A+B), but it appears that one power feed has been lost. At this time, all services remain operational; however, they should be considered AT RISK due to the loss of redundancy. We will provide further updates as the investigation progresses.

  2. investigating Oct 22, 2026, 03:25 PM UTC

    EXN appear to have lost all power in one rack which has caused a shutdown of our vDC enviroment and support portal. We are actively escalating this within Virtus. Please use [email protected] for communications.

  3. investigating Oct 22, 2026, 03:41 PM UTC

    Power has been restored to the rack in question. Our teams are continuing efforts to restore the vDC platform.

  4. investigating Oct 22, 2026, 03:51 PM UTC

    vDC resources are recovering. EXN are dispatching an engineer to site.

  5. identified Oct 22, 2026, 04:54 PM UTC

    vDC resources have recovered, if any clients continue to have issue, please raise a ticket via the Client Portal. EXN have dispatched an engineer to work with Virtus and confirm the power status to all racks. The site remains AT-RISK

  6. resolved Oct 22, 2026, 10:46 PM UTC

    Full redundancy has now been restored, and as a precaution, a number of PDUs replaced in Virtus Enfield. EXN will continue investigations with Virtus over coming days, and a full PIR will be issued to affected clients.