EX Networks incident

Global Switch London 2

Resolved after 2 days 11 hours, affecting Global Switch London East (formerly Global Switch 2) and Virtual Data Centre (vDC) - Global Switch East, on June 23, 2026.

monitoring Jun 24, 2026, 01:43 PM UTC

The DC has confirmed a plan to restore redundancy. For more details, we ask clients to raise a ticket via the usual channels.

Started
Jun 23, 2026, 07:43 PM UTC
Resolved
Jun 26, 2026, 06:45 AM UTC
Duration
2d 11h
Detected by Pingoru
Jun 23, 2026, 07:43 PM UTC

Affected components

Global Switch London East (formerly Global Switch 2)Virtual Data Centre (vDC) - Global Switch East

Update timeline

  1. investigating Jun 23, 2026, 07:43 PM UTC

    We are currently investigating a potential power issue within Global Switch 2.

  2. investigating Jun 23, 2026, 07:59 PM UTC

    Power appears to have returned, we're still waiting for information from the data centre and our teams are working on bringing online various internal systems hosted out of GS2, this includes our Client Portal. Support team is available on [email protected] in the interim.

  3. monitoring Jun 23, 2026, 09:03 PM UTC

    Power has remained stable, internal services including the Client Portal are back up and functioning. Client vDC resources are now being verified.

  4. monitoring Jun 23, 2026, 09:31 PM UTC

    Power has remained stable and services have been restored. If any clients require assistance, please raise a ticket by logging into our portal. We're still waiting for any official communications from Global Switch; however, we believe this power outage affected both feeds across multiple floors.

  5. monitoring Jun 24, 2026, 04:03 AM UTC

    The DC has confirmed a brief power loss occurred at approximately 20:25 following a UK Power Networks (UKPN) power quality issue that triggered the site's protection systems. The site transferred to DRUPS at 20:35 as designed; during transfer, the DRUPS switched to bypass, causing an interruption. Power has since been restored to all racks. The site remains at risk. If you continue to experience issues, please log a case via the support portal with details of the affected device(s) and their location, and make use of any available workarounds or DR systems in the interim. We will provide a further update as soon as more information is available.

  6. monitoring Jun 24, 2026, 01:43 PM UTC

    The DC has confirmed a plan to restore redundancy. For more details, we ask clients to raise a ticket via the usual channels.

  7. resolved Jun 26, 2026, 06:45 AM UTC

    Both the A+B feeds are back on DRUPS and full redundancy has been restored.