TeraSwitch incident

SGP2 - Internet Connectivity Loss

Critical Resolved View vendor source →

TeraSwitch experienced a critical incident on July 17, 2026 affecting SGP2 - Singapore, lasting 2h 12m. The incident has been resolved; the full update timeline is below.

Started
Jul 17, 2026, 11:45 PM UTC
Resolved
Jul 18, 2026, 01:57 AM UTC
Duration
2h 12m
Detected by Pingoru
Jul 17, 2026, 11:45 PM UTC

Affected components

SGP2 - Singapore

Update timeline

  1. investigating Jul 17, 2026, 11:45 PM UTC

    Teraswitch is investigating reports of Internet connectivity loss at SGP2. We will provide an update shortly.

  2. identified Jul 18, 2026, 12:22 AM UTC

    Teraswitch has isolated this incident to a vendor power maintenance event with unexpected impact, affecting both of our network racks and causing an Internet connectivity loss at SGP2. Customer services are believed to be powered on without upstream connectivity. Facility staff are at work to restore Internet connectivity and bring the site back online. We will provide an update as soon as possible.

  3. resolved Jul 18, 2026, 01:57 AM UTC

    Our facility partner has restored power to Teraswitch's SGP2 network racks. Root cause: both redundant PDUs in each network rack were fed by power breakout boxes connected to the same overhead electrical bus bar, creating a single point of failure. Facility engineers relocated one breakout box to the correct bus, restoring power to the network equipment and eliminating the single point of failure. We expect no further impact at this time. Customer systems did not lose power at any point during this event.